Impuls-Adapter - {nbsp}{nbsp}{nbsp} · Zubehör zu Klimadaten-Logger


Impuls-Adapter

 Best.Nr.  Ausführung  Preis 
 S-UC-B-M006  2 Hz  110.0099.0093.00 Fr. 
 S-UC-A-M006  120 Hz  110.0099.0093.00 Fr. 

Pulse Input Adapters (Part #’s S-UCA-M006 and S-UCB-M006)

 The Pulse Inputs Adapters are ideal for connecting a wide range of sensors with pulse outputs such as tipping-buck rain gauges, flow meters, power meters and gas meters. These adapters count the number of pulses per logging interval.

 Electronic Switch Version (S-UCA-M006)

Compatibility: Electronic switch closures, such as FET or open-collector outputs, or CMOS-level logic signals

Maximum input frequency: 120 Hz (120 pulses per second)

Lockout time: 45 micro-sec +/-10%

Preferred pulse polarity*: Active low

 Contact Closure Version (S-UCB-M006)

Compatibility: contact closures, such as tipping-bucket rain gauges or reed switches

Maximum input frequency: 2 Hz (2 pulses per second)

Lockout time (for switch debounce): 327 milli-sec +/-10%

Preferred switch type*: normally-open

 Common Specifications

Measurement Range: 0-4093 counts per logging interval (data must be exported for conversion to other units)

Minimum Pulse Width: 1 ms

Maximum input voltage: 3.6V

Minimum input voltage: -0.3V

Logic levels: low <= 0.6V high >=2.7V

Edge detection: falling edge

Input/Output impedance: 100 kilohms

User connection: 2-wire input (24 AWG wire 2 wire nuts included)

Cable length: 6.5m (21 ft) (only adds 50cm of smart sensor cable)

Weight: 310 g (11 oz)

# Data Channels: 1

 * Pulses of opposite polarity can be used, but battery usage rate will be higher.

Klicken Sie hier um in den Shop zu gelangen